X9=4%/100×100/0.22=0.18

X12=0.1075

X13=0.0625 X14=0

(a)

X15=7.7×6.8/(7.7+6.8)+2.95=6.56

(b) (c) X?= X12‖(X13+ X9)‖X15=0.09

32

I*=1/ X?=11.1

短路电流有名值:

I?=I*sj/3uav=5.58KA

冲击电流:

ich=2×1.8×5.58=14.2

最大电流有效值:

Ich=15.58×1.51=8.43

短路容量:

s?=3×5.58×115=1111.4

K2点短路时:

X15=7.7×6.8/(7.7+6.8)+2.95=6.56

` (d) (e) (f)

X17= X15‖(X9+ X13)=0.72 X?= X12+ X17=0.83

33

I*=1/ X?=1/0.83=1.2

短路电流有名值:

I?=I*sj/3uav=1.85KA

冲击电流:

ich=2×1.8×1.85=4.7

最大电流有效值:

Ich=1.85×1.51=2.8

短路容量:

s?=3×1.85×37.5=120.2

K3点短路时:

X18=X14 +X15=6.56 X19= X12‖X18=0.106

(g)

(h)

X?= (X19+ X13) ‖X9=0.145

34

(i)

I*=1/ X?=1/0.145=6.9

短路电流有名值:

I?=I*sj/3uav=38KA

冲击电流:

ich=2×1.8×38=96.7

最大电流有效值:

Ich=38×1.51=57.4

短路容量:

s?=3×38×10.5=691

K4点短路时:

X18=X14 +X15=6.56 X19= X12‖X18=0.106

(j)

(k)

35

(l)