报警调试方案.. 下载本文

目录

一、工程简介 ....................................................................................................... 1 二、工程范围 ....................................................................................................... 1 三、工程特点 ....................................................................................................... 1 四、编制依据 ....................................................................................................... 4 五、调试内容及方法 ........................................................................................... 5 5.1消防广播及电话系统调试 .......................................................................... 5 5.2防火阀控制系统调试 .................................................................................. 6 5.3气体灭火装置调试 ...................................................................................... 6 5.4消防联动控制器调试 .................................................................................. 7 5.5火灾报警系统装置调试 .............................................................................. 8 5.6图型显示装置调试 ...................................................................................... 9 5.8系统整体联动调试 .................................................................................... 10 六、安全保证措施 ............................................................................................. 11

一、工程简介

本项目火灾报警系统形式为控制中心报警系统,火灾报警设备采用总线制,系统由火灾探测器、手动火灾报警按钮、火灾声光警报器、消防应急广播、消防专用电话、气体灭火控制盘、缺氧报警控制器等。

二、工程范围

一二层高低压配电间、UPS室、电池间、UPS/HVDC间、空调间、

冷冻站、气瓶间、微模块间、强弱电室、走廊等公共区域。

三、工程特点

1、自动报警系统

火灾报警系统由自动报警系统、联动控制系统、极早期烟雾探测系统、消防紧急广播、消防通讯系统组成,与一期共用消防报警中心。 2、消防联动控制 2.1 排烟系统的联动控制

(1)自动控制方式,由同一防烟分区内的两只独立的火灾探测器或一只火灾探测器与一只手动火灾报警按钮的报警信号,作为排烟阀(口)开启的联动触发信号,由消防联动控制器联动控制排烟阀(口)的开启,同时停止该防烟分区的空气调节系统;排烟阀(口)开启的联动反馈信号作为排烟风机启动的联动触发信号,由消防联动控制器联动控制排烟风机的启动。 (2)手动控制方式,在消防控制室内的消防联动控制器上手动控制送风

1