iculties,shallconsistofminingorganizationstosolveproblems.C-class:fromsegmentsandbusinessrisksthatmustbeaddressedintheDepartment.2,open-pitmineunsafetypesinclude:electrical,transport,blasting,fire,andotherslope.3,accordingtotheseverityofthehazardfilledinbyunittroubleshooting,registrationform(seeatteaintheaccidentinvestigation,managementandreporting,eachpostshouldbedevelopedunderthissystemspecialistscheck,cleartheexaminations,time,cyclesandotherrelevantregulations.Strengtheningsitesupervisionandexamination,todetectandinvestigateillegalcommand,illegaloperationsandviolationsofoperatingrules.Secondsafetyreferstotheproductionsite,technologymanagement,equipment,facilities,andsooncanleadtoaccidentsrisksexist.1,accordingtotheextentofthesecurityrisks,solvingisdividedintoa,b,andclevelsofdifficulty;A-level:difficult,miningdifficulties,shallbereportedtothecompany'sproblems.B-class:difficulttoresolvedif3.2 什么是保护安装处的负荷阻抗、短路阻抗、系统等值阻抗?
答:负荷阻抗是指在电力系统正常运行时,保护安装处的电压(近似为额定电压)与电流(负荷电流)的比值。因为电力系统正常运行时电压较高、电流较小、功率因数较高(即电压与电流之间的相位差较小),负荷阻抗的特点是量值较大,在阻抗复平面上与R轴之间的夹角较小。
短路阻抗是指在电力系统发生短路时,保护安装处的电压变为母线残余电压,电流变为短路电流,此时测量电压与测量电流的比值即为短路阻抗。短路阻抗即保护安装处与短路点之间一段线路的阻抗,其值较小,阻抗角较大。
系统等值阻抗:在单个电源供电的情况下,系统等值阻抗即为保护安装处与背侧电源点之间电力元件的阻抗和;在多个电源点供电的情况下,系统等值阻抗即为保护安装处断路器断开的情况下,其所连接母线处的戴维南等值阻抗,即系统等值电动势与母线处短路电流的比值,一般通过等值、简化的方法求出。
3.3 什么是故障环路?相间短路与接地短路所构成的故障环路的最明显差别是什么?
答:在电力系统发生故障时,故障电流流通的通路称为故障环路。 相间短路与接地短路所构成的故障环路的最明显差别是:接地短路点故障环路为“相—地”故障环路,即短路电流在故障相与大地之间流通;对于相间短路,故障环路为“相—相”故障环路,即短路电流仅在故障相之间流通,不流向大地。
3.4 构成距离保护为什么必须用各种环上的电压、电流作为测量电压和电流?
答:在三相电力系统中,任何一相的测量电压与测量电流之比都能算出一个测量阻抗,但是只有故障环上的测量电压、电流之间才满足关系
Um?ImZm?ImZk?ImZ1Lk,即由它们算出的测量阻抗才等于短路阻抗,才能够正确
反应故障点到保护安装处之间的距离。用非故障环上的测量电压与电流虽然也能算出一个测量阻抗,但它与故障距离之间没有直接的关系,不能够正确地反应故障距离,所以不能构成距离保护。
3.10 解释什么是阻抗继电器的最灵敏角,为什么通常选定线路阻抗角为最灵敏角。
iculties,shallconsistofminingorganizationstosolveproblems.C-class:fromsegmentsandbusinessrisksthatmustbeaddressedintheDepartment.2,open-pitmineunsafetypesinclude:electrical,transport,blasting,fire,andotherslope.3,accordingtotheseverityofthehazardfilledinbyunittroubleshooting,registrationform(seeatteaintheaccidentinvestigation,managementandreporting,eachpostshouldbedevelopedunderthissystemspecialistscheck,cleartheexaminatons,time,cyclesandotherrelevantregulations.Strengtheningsitesupervisionandexamination,todetectandinvestigateillegalcommand,illegaloperationsandviolationsofoperatingrules.Secondsafetyreferstotheproductionsite,technologymanagement,equipment,facilities,andsooncanleadtoaccidentsrisksexist.1,accordingtotheextentofthesecurityrisks,solvingisdividedintoa,b,andclevelsofdifficulty;A-level:difficult,miningdifficulties,shallbereportedtothecompany'sproblems.B-class:difficulttoresolvedif 答:当测量阻抗角Zm的阻抗角与正向整定阻抗Zset1的阻抗角相等时,阻抗继电器的动作阻抗最大,正好等于Zset1,即Zop?Zset1,此时继电器最为灵敏,所以
Zset1的阻抗角又称为最灵敏角。
选定线路阻抗角为最灵敏角,是为了保证在线路发生金属性短路点情况下,阻抗继电器动作最灵敏。
3.15 以记忆电压为参考的距离继电器有什么特点?其初态特性与稳态特性有何差别?
答:以记忆电压为参考电压的距离继电器可以消除所有故障点死区,尤其是克服出口三相对称性短路时三相电压都降为0而失去比较依据的不足;但其动作性不能长期保持。
初态特性与稳态特性差别:(1)在传统的模拟式距离保护中,记忆电压是通过LC谐振记忆回路获得的,由于回路电阻的存在,记忆量是逐渐衰减的,故障一定时间后。记忆电压将衰减至故障后的测量电压。所有由记忆回路产生的结论仅在故障刚刚发生、记忆尚未消失时是成立的,因此称之为初态特性;(2)数字式保护中,记忆电压就是存放在存储器中的故障前电压的采样值,虽然不存在衰减问题,但故障发生一定时间后,电源的电动势发生变化,将不再等于故障前的记忆电压,再用故障前的记忆电压作为参考电压,特性也将发生变化。所以记忆电压仅能在故障后的一定时间内使用,例如仅在I、II段中采用。
4.18 试述电流相位纵联差动保护原理比纵联电流差动保护原理的优缺点,实现技术要求方面的优缺点。
答:电流相位纵联差动保护是依据两端电流相位的差异来甄别区内、外故障的。在输电线路正常运行及外部故障时,流过线路两端的电流为同一个电流,在电流参考方向均由母线指向被保护线路的情况下,两侧电流的相位相反,即相位差为180°;而在线路内部故障时,两侧电源均向故障点提供短路电流,所以两端电流的相位差取决于两端电动势的相位差,一般不超过100°。电流相位纵联差动保护由于仅需要比较两端电流的相位信息,动作情况与电流的大小无关,在模拟式保护中实现较为方便,并且受TA饱和的影响稍小;其缺点是两端电流的相位受分布电容的影响较大,闭锁角整定比较困难,闭锁角过大可能导致内部