500 kV 变电站主变压器中压侧失灵判据缺陷分析及应对策略

500 kV 变电站主变压器中压侧失灵判据缺陷分析及应对策

李凡红;肖启繁;邹瑜;庄秋月

【期刊名称】《四川电力技术》 【年(卷),期】2013(000)005

【摘要】500 kV变电站主变压器中压侧失灵判据的目的是为了中压侧开关失灵之后通过主变压器后备保护来跳三侧开关,隔离中压侧故障点,避免电网事故的扩大。失灵启动必须满足两条件:一是保护动作不返回;二是存在失灵电流。当在特殊区域发生故障时,若两者配合不好将引起保护的拒动,故障不能及时切除,将会影响主变压器设备的安全及电网的稳定。基于此,以某500 kV变电站主变压器保护配置为例来分析其隐患,并提出相应的对策,希望对此类工程设计和二次验收提供一定的实用参考价值。%The failure criterion in medium -voltage side of main transformer in 500 kV substation are designed to trip three sides through the backup protection of main transformer when the medium -voltage side breaker failed to jump , so as to isolate the fault point in medium -voltage side and avoid the expansion of the accident in power grid .The malfunction start-up must meet the following two conditions:the protection lasting action and failure current .When the failure occurs in a special area , a bad combination of the two factors will cause the protection to refuse to trip , and the fault cannot be removed , which will in-fluence the security of main transformer equipment and the stability of the grid .On

this basis, taking the protection configura-tions of main transformer in a 500 kV substation for example , the hidden dangers are analyzed and the appropriate counter-measures are proposed , which provides some practical references for such engineering design and secondary acceptance .

【总页数】4页(69-72)

【关键词】中压侧失灵判据;TA配置;故障假定模拟;断路器 【作者】李凡红;肖启繁;邹瑜;庄秋月

【作者单位】国网四川省电力公司检修公司,四川成都 610041;国网四川省电力公司检修公司,四川成都 610041;国网四川省电力公司检修公司,四川成都 610041;国网四川省电力公司检修公司,四川成都 610041 【正文语种】中文 【中图分类】TM835 【文献来源】

https://www.zhangqiaokeyan.com/academic-journal-cn_sichuan-electric-power-technology_thesis/0201232165120.html 【相关文献】

1.500 kV 变电站主变压器低压侧开关分闸回路典型缺陷分析及处理措施 [J], 陈宏元; 李凡红; 庄秋月

2.500 kV变电站主变压器低压侧并联电容器组布置优化 [J], 盛晶晶 3.试析500kV 变电站主变压器的运行和维护策略 [J], 崔仲源

4.让延安750kV智能变电站的“心脏”更强劲——西北电能监理延安750kV

智能变电站主变压器纪实 [J], 李革; 赛夫; 相里子鹏

5.500kV某变电站500kV主变保护第二组中失灵解复压无电流判据隐患整改技术报告 [J], 王昕

以上内容为文献基本信息,获取文献全文请下载

联系客服:779662525#qq.com(#替换为@) 苏ICP备20003344号-4