龙源期刊?/p>
http://www.qikan.com.cn
浅谈
10kV
配电网中电阻接地设计
作者:?/p>
?/p>
来源:《价值工程?/p>
2010
年第
30
?/p>
摘要
:
本文主要探讨?/p>
10kV
配电网的电阻接地设计问题
,
在我国目?/p>
10kV
配电网主要采?/p>
三种方式进行接地
,
包括
:
中性点不接地、中性点经消弧线圈接地以及中性点经电阻接?/p>
,
这三?/p>
接地方式各有优缺?/p>
,
适用范围各不相同。除了介绍主要接地方式外
,
本文还就接地实践中应?/p>
注意的事项进行了分析
,
提出了有效建议?/p>
Abstract: The paper discusses mainly the design of resistance grounding of 10kV distribution
network. Three ways are adopted for the grounding of China's 10kV distribution network
now,including neutral,neutral and arc suppression coil grounding and the resistance grounding through
neutral point. These three grounding methods have their advantages and disadvantages and their using
scope varies. Besides introducing the main grounding methods,the paper also discusses the noting
points in the grounding practice and proposes the effective suggestions.
关键?/p>
:10kV
配电?/p>
;
电阻接地设计
;
中性点
Key words: 10kV distribution network;resistance grounding design;neutral point
中图分类?/p>
:TM72
文献标识?/p>
:A
文章编号
:1006-4311(2010)30-0251-01
110kV
配电网主要接地方?/p>
1.1
中性点不接地系统方式中性点不接地系统的主要优点在于单相接地故障时的稳态工?/p>
电流?/p>
,
在发生雷击绝缘闪络等瞬时性故障时可自行消除不会跳?/p>
,
单相接地时可带故障运行二
个小?/p>
,
提高了供电的可靠?/p>
,
同时由于人地电流小也降低了地电位升高和对通信系统等的干扰
影响
;
其缺点主要是单相接地故障时产生的过电压高
,
对弱绝缘击穿概率?/p>
,
因此要求电气设备?/p>
缘水平高
,
在间歇性电弧接地故障时产生较高的弧光接地过电压及高频振荡电?/p>
,
有可能使故障
扩大引发相间短路
,
同时由于单相接地时短时不跳闸继续带故障运?/p>
,
此时若相邻线路的非故?/p>
相又因过电压而接地则将发展成两相接地短路使事故扩大?/p>
1.2
中性点经消弧线圈接地对于供电可靠性要求较高而接地电容电流又超过规范允许值的
以架空线为主的配?/p>
,
可考虑采用中性点经消弧线圈的接地方式。电网中性点通过消弧线圈?/p>
地的目的在于给故障点注入电感电流以抵消电容电?/p>
,
把接地故障电流降低到允许范围?/p>
,
使接
地电弧易于自熄以消除弧光间隙接地过电压?/p>
1.3
中性点经电阻接地工程中常用的中性点经电阻接地方式可分为三种
:
经高电阻接地、经
中电阻接地和经小电阻接地。中性点经高电阻接地是指当接地电容电流超过允许值时
,
可采?